3 connecting the spc200 via a branch line, Connecting the spc200 via a branch line – Festo Кабели и принадлежности User Manual
Page 45
3. Installation
3−9
Festo P.BE−SPC200−COM−PDP−E N en 0901c
3.3
Connecting the SPC200 via a branch line
Please note
If connection of the SPC200 via a branch line cannot be
avoided:
Ĉ Do not connect the branch lines with a terminating
resistor.
Ĉ Please note that the permitted segment length will be
reduced by the length of the branch line.
Ĉ Please note the maximum permitted branch line lengths.
If possible, branch lines should be avoided on the
PROFIBUS−DP, as they can cause too much capacitive
stress on the transmission cable.
Baud rate
(in kBaud)
Maximum permitted branch line length
(in m)
9.6
19.2
93.75
187.5
500
1500
3000 ... 12000
500
500
100
33.3
20
6.6
Not permitted