4. Commissioning
4−16
Festo P.BE−SPC200−COM−PDP−E N en 0901c
The address range with DP identifiers is described under
PROFIBUS−DP. The DP identifiers can be entered via a diaĆ
logue or directly in the configuration tables of the configurĆ
ation program. The method of handling depends on the conĆ
figuration program.
Rules for configuring the I/O address range
ć
In the case of the I/O signals, use a DP identifier for the
inputs and a different DP identifier for the outputs. The
DP identifiers which are permitted here depend on the
operating mode of the SPC200 used (see section 4.4.3).
ć
If the parameter channel is to be used:
use a DP identifier for the parameter channel (see also
section 4.4.4).
ć
If actual positions are to be transmitted to the DP master:
use a DP identifier for each axis (see also section 4.4.5).
ć
All non−configured output addresses can be used as flags
in the operating mode Start/Stop. If, for example, the
DPĂidentifier 16DI is used for inputs of the master, the
outputs Q11.0...Q13.15 of the SPC200 can be used as
flags (see also Fig. 4/5).
In this manual hexadecimal DP identifiers are marked by a
subscript h". Decimal DP identifiers are marked with a subĆ
script d".