4. Commissioning
4−19
Festo P.BE−SPC200−COM−PDP−E N en 0901c
4.4.4 DP identifiers for the parameter channel (optional)
In order to use the parameter channel, you will require:
ć
a field bus module with firmware version as from V 2.0
ć
the SPC200 with operating system version as from V 4.6
ć
WinPISA as from version 4.3.
For the parameter channel data consistency is only permitted
over the complete length. If the parameter channel is to be
used, the DP identifier must be entered once.
Further information on the parameter channel of the SPC200
can be found in chapter 5.
Parameter
channel
Address range
DP identifiers
channel
EN 50170
Siemens
EN 50170
Siemens
Consistent over
1 byte
Complete length
4 I/O words
4 I−words
4 O−words
*)
*)
F3
h
4AX
*)
Data consistency only permitted over complete length
Fig. 4/9: DP identifiers for the parameter channel