6. Diagnosis and error treatment
6−7
Festo P.BE−SPC200−COM−PDP−EN en 0901c
Information
Meaning
(Bus status) parametrizing
No connection to the field bus; the SPC200 waits for
parametrizing by the master
(Bus status) configuring
Waits for configuration by the PROFIBUS master
(Bus status) data exchange
Data exchange runs, normal operating status
(Bus status) baud rate search
Automatic baud rate recognition
SYNC active
PROFIBUS control command active (see section 4.4.1)
FREEZE active
SYNC and FREEZE active
Hardware fault
Carry out system reset or switch on SPC200 again; if fault occurs
again, replace SPC200
Station address not valid
Correct PROFIBUS address
Operating mode not valid
The operating mode set is not supported. Set the correct
operating mode.
No connection to the SPC200
Carry out system reset or switch on SPC200 again
Field bus card not yet
initialized
Carry out system reset or switch on SPC200 again
Config. incorrect (SPS master)
I/O configuration of the master faulty. I/O configuration of the
master must match the configuration of the SPC200 (see rules on
configuration in section 4.4.2).
Not initialized
The field bus card has not yet been initialized. Carry out system
reset or switch on SPC200 again; if fault occurs again, replace
SPC200
Fig. 6/3: Status information on faults