6. Diagnosis and error treatment

6−7

Festo P.BE−SPC200−COM−PDP−EN en 0901c

Information

Meaning

(Bus status) parametrizing

No connection to the field bus; the SPC200 waits for
parametrizing by the master

(Bus status) configuring

Waits for configuration by the PROFIBUS master

(Bus status) data exchange

Data exchange runs, normal operating status

(Bus status) baud rate search

Automatic baud rate recognition

SYNC active

PROFIBUS control command active (see section 4.4.1)

FREEZE active

SYNC and FREEZE active

Hardware fault

Carry out system reset or switch on SPC200 again; if fault occurs
again, replace SPC200

Station address not valid

Correct PROFIBUS address

Operating mode not valid

The operating mode set is not supported. Set the correct
operating mode.

No connection to the SPC200

Carry out system reset or switch on SPC200 again

Field bus card not yet
initialized

Carry out system reset or switch on SPC200 again

Config. incorrect (SPS master)

I/O configuration of the master faulty. I/O configuration of the
master must match the configuration of the SPC200 (see rules on
configuration in section 4.4.2).

Not initialized

The field bus card has not yet been initialized. Carry out system
reset or switch on SPC200 again; if fault occurs again, replace
SPC200

Fig. 6/3: Status information on faults