beautypg.com

Festo Кабели и принадлежности User Manual

Page 129

background image

6. Diagnosis and error treatment

6−9

Festo P.BE−SPC200−COM−PDP−EN en 0901c

The method of requesting the slave diagnosis can be found in
the manual for the DP master.

If the device−related diagnosis is not treated, this results in a
stop of the PLC. The message can therefore be suppressed
(see section 4.2.2, Fig. 4/4).

Station status 1

With station status 1 bit 3 is especially of interest. If this bit is
set, it is sensible to evaluate the device−related diagnosis.

Station status 1

Bit

Meaning

Explanation

0

Diag.Station_Non_Existent

SPC200 is no longer/not yet addressable.
Possible causes:
Ĉ operating voltage not applied
Ĉ data cable interrupted
Ĉ fault in data cable

1

Diag.Station_Not_Ready

SPC200 is not yet ready for data exchange

2

Diag.Cfg_Fault

The configuration data received from the master do not
agree with those ascertained by the SPC200.

3

Diag.Ext_Diag

There is a device−related diagnosis.

1)

4

Diag.Not_Supported

1 = The bit is set if the SPC200 does not support the

function requested.

5

Diag.Invalid_Slave_Response

Always 0 (always reset to 0 by the SPC200)

2)

6

Diag.Prm_Fault

Last parametrizing telegram faulty

7

Diag.Master_Lock

Access by a different master (set by the master)

1)

Is set by the SPC200 when a new fault occurs (new fault message).

2)

Is set to 1 in the DP master if the reply sent by the slave cannot be interpreted.

Fig. 6/4: Structure of station status 1

This manual is related to the following products: