6. Diagnosis and error treatment
6−9
Festo P.BE−SPC200−COM−PDP−EN en 0901c
The method of requesting the slave diagnosis can be found in
the manual for the DP master.
If the device−related diagnosis is not treated, this results in a
stop of the PLC. The message can therefore be suppressed
(see section 4.2.2, Fig. 4/4).
Station status 1
With station status 1 bit 3 is especially of interest. If this bit is
set, it is sensible to evaluate the device−related diagnosis.
Station status 1
Bit
Meaning
Explanation
0
Diag.Station_Non_Existent
SPC200 is no longer/not yet addressable.
Possible causes:
Ĉ operating voltage not applied
Ĉ data cable interrupted
Ĉ fault in data cable
1
Diag.Station_Not_Ready
SPC200 is not yet ready for data exchange
2
Diag.Cfg_Fault
The configuration data received from the master do not
agree with those ascertained by the SPC200.
3
Diag.Ext_Diag
There is a device−related diagnosis.
1)
4
Diag.Not_Supported
1 = The bit is set if the SPC200 does not support the
function requested.
5
Diag.Invalid_Slave_Response
Always 0 (always reset to 0 by the SPC200)
2)
6
Diag.Prm_Fault
Last parametrizing telegram faulty
7
Diag.Master_Lock
Access by a different master (set by the master)
1)
Is set by the SPC200 when a new fault occurs (new fault message).
2)
Is set to 1 in the DP master if the reply sent by the slave cannot be interpreted.
Fig. 6/4: Structure of station status 1