9.8 Operating Data I/O

9.8.1 Current Output

Depending on the version, the outputs and inputs to be connected passively or actively and / or
to NAMUR EN 60947-5-6! The tables in section 9.7 show which I/O version and which inputs
and outputs are installed in your signal converter.See the sticker inside the cover of the termi-
nal compartment.

All current outputs are galvanically separated from each other and from all other circuits.

Depending on the version, up to 3 current outputs in parallel can be built in, one always with
HART® communication (except for Foundation Fieldbus and PROFIBUS).

Passive mode:

external power supply Uext

a

32 V DC @ I

a

22 mA

Active mode:

load impedance RL

a

1 k

Ω at 1

a

22 mA (not applicable to EEx-i, see separate

Ex – operating instructions)

Self-monitoring interruption of mA loop or

load impedance too high in mA loop

Factory-set data and functions are given in the enclosed report on settings.

All operating data and functions are settable, see section 10.4.

Error message via status output (see Fct. C 3.x.1).

Current value for error identification adjustable, see Fct. C 3.x.3 (current output).

Range change, automatically by status output or manually by control input, see Sect. 10.4, Fct.
C 3.x.11 and C 3.x.12 (for current output) and Fct. C 3.x.01 (for status output or control input).

Setting range threshold: 5...80% of Q100%, ± 0...5% hysteresis (appropriate ratio from low to
high range of 1:20 to 1:1.25).

The active range is signalled via a status output.

Forward / reverse flow measurement (F/R mode) is possible, see Fct. C 3.x.7 (current output)
and Fct. C 3.x.1 (status output).

Connection diagrams, see s.9.9

Warning:

For installations in hazardous areas, reference MUST also be made to the guidelines for the
use of coriolis meters in hazardous areas!