109

Ref

Display

Description & Settings

C 3.x

Current output X ctd...

C3 x.6

Range

0 … xx.xx (format and unit depends on measured variable, see C3 .x.05)

C3 .x.7

Polarity

Both polarities

Plus and minus values are used

Positive polarity

Negative values are set to 0%

Negative polarity

Positive values are set to 0%

Absolute

Absolute value is used

Choice of meas. value polarity, note flow direction, see C 1.5.1

C.3.z.8

Limitation

± xxx … ± xxx % (setting range -150 %

a

value

a

+150 %)

C 3.x.9

Low flow cutoff

xx.x ± xx.x %

(setting range: 0.0 %…20 %)
1st value = operating point
2nd value = hysteresis
(condition: 2nd value

a

1st value)

C 3.x.10

Time constant

xxx.x s

(setting range 000.1 s…100.0 s) Time constant for
Current Output X

C 3.x.11

Special function

OFF:

switched off

Automatic range: switched on - for indication

status output accordingly

External range:

switched on- for external range change
Activate control input accordingly

C 3.x.12

Threshold

Appears only when Fct. C 3.x.11 activated, see above.
Set switching point for automatic range or external range; defines the
rangeability

xx.x ± xx.x %

(setting range: 5.0 %…80 %)
1st value = operating point
2nd value = hysteresis
(condition: 2nd value

a

1st value)

C 3.x.13

Information

Displays the Serial No, Software No and calibration date of the circuit
board

C 3.x.14

Simulation

Sequence, see Test Level Menu, Fct. B 1

C 3.x.15

4mA trimming

Set actual value for 4mA.

C 3.x.16

20mA trimming

Set actual value for 20mA.

In the following descriptions for the frequency output, "x“ denotes the terminals:
C 3.2 = A

C 3.3 = B

C 3.5 = D

C 3.x

Frequency output X

C 3.x.1

Pulse shape

Automatic

approx. pulse width in [ms] = 500 / (max. pulse rate in
[1/s])

Symmetrical: pulse duty factor approx. 1:1

Fixed

set in Fct. C 3.x.2

C 3.x.2

Pulse width

Appears only when "fixed“ activated in Fct. C 3.x.01 Pulse Shape, see
above

xxx.xx ms

(setting range: 0.05…2000 ms) (Note:
max. setting value Tp [ms]

a

500.00 / (max. pulse rate

[1/s] )

C 3.x.3

100 % Puls rate

xxxxx.x Hz

(setting range 00000.00…10000.0 Hz)
limitation at 100% pulse rate

a

100 Hz: Imax

a

100 mA

limitation ati 100% pulse rate > 100 Hz:Imax

a

20 mA