beautypg.com

Yokogawa PC-Based MX100 User Manual

Page 76

background image

2-62

IM MX180-01E

Turnng Transmsson Output ON and OFF Collectvely for Analog Output/PWM
Output

1.

From the Action menu, choose Transmission output.

Transmission output on all active channels on the AO and PWM channel tabs is started (All
ON).

2.

From the Action menu, choose Transmission output again.

Transmission output on all active channels on the AO and PWM channel tabs is held at the
values that were in use immediately before this operation was carried out.

Explanaton

Settng up Output for AO Channels

Transmission Output: Values measured on the MX100, or computed values

corresponding to computed results set on computation channels
are converted to analog voltages (–10.000 V to 10.000 V) or
analog current (0.000 mA to 22.000 mA) and output.

Note

The output range is –11.000

to

11.000 V or 0.000

to

22.000 mA, but the span setting range is

–10.000

to

10.000 V or 0.000

to

20.000 mA.

User Output:

You can set the analog voltage or analog current to an arbitrary
value in the monitor screen. The setting ranges are –10.000 to
10.000 V (voltage), or 0.000 to 20.000 mA (current).

Setting the User Output of the Voltage Value

Setting the User Output of the Current Value

Click to switch the display

Drag the pointer to set

Click the input box, and enter a value

Settng up Output for PWM Channels

Transmission Output: Outputs a duty pulse waveform corresponding to values

measured on the MX100, or the computed results set on the
computation channels.

User Output:

You can set the pulse duty ratio (0.000 to 100.000%) to an
arbitrary value in the monitor screen.

Pulse interval

Output width

Duty ratio =

x 100 [%]

output width

pulse intrvl

2.11 Analog/PWM Output Settngs