Index pwm output settngs – Yokogawa PC-Based MX100 User Manual
Page 75
2-61
IM MX180-01E
Integrat
on Mon
tor
3
2
1
4
5
App
Index
PWM Output Settngs
Selection of output
action upon errors
Transmission output
reference channel
Sets the output value upon
startup or error occurrence
Selection of output
value upon startup
Selection of output action upon errors
Minimum/Maximum value
of output span
Select output or no output
Enter the pulse interval coefficient
Select the resolution
of the pulse output
1.
Click Channel to show the Channel setup screen.
2.
Click the PWM Channel tab.
3.
Select the Use check boxes for the PWM channels you wish to output.
4.
Specify a channel action of Transmission output or User output. If user output is
specified, you can enter settings in the monitor screen.
Only one of all the AO and PWM channels can be selected for user output.
5.
When transmission output is specified, enter the Reference channel.
The reference channel cannot be entered if the channel operation is user output.
6.
Click the Min box or Max box under Span and enter the minimum or the maximum
value of the span.
7.
Click the Power ON box under Output Action and select Hold previous value or
Preset value.
8.
Click the Error box under Output Action and select Hold previous value or Preset
value.
9.
If you select Preset value under Output Action, click Preset value, and enter the
duty.
10.
Select 1 msec or 10 msec in the Resolution list box under Pulse.
Click the Interval (msec) box under Pulse, and enter the pulse interval coefficient.
2.11 Analog/PWM Output Settngs