2.2 Confgurng the System, Settng the Wrte Mode
of the CF Card, and Formattng the CF Card
Procedure
Reconfgurng the System
If you change the attachment positions or type of the input/output modules you must
carry out the procedure below.
Note
• If you change the MX100 input/output modules, a message, “Some detected modules do
not match the current software configuration. Rebuild based on the current MX hardware
setup?” appears when you start the Integration Monitor. Current configuration refers to the
module configuration (attachment positions and types of modules) that is detected by the
software. To match the current configuration with the actual module configuration (referred
to as reconfiguring the system), click Yes. If you reconfigure, the settings (measurement
conditions, etc.) of the modified modules are initialized. The reconfigured module
configuration can be confirmed on the System screen that appears by clicking System. If
you Click No, the connection is made without reconfiguration, and the module settings are
left unchanged.
• Turn OFF the power to the MX100 when attaching or detaching input/output modules.
1.
Click System to show the System setup screen.
Click here
2.
Click the Actual Configuration tab followed by the Retrieve current configuration
button.
An X mark is displayed on the changed modules.
Click here
Click here
Changed modules
Note
• The × mark appears at slots where the module has been changed, and which are not
operating correctly.
• The serial number is not displayed to the right of the module type (MX115-D05-H10, MX125-
MKC-M10, MX114-PLS-M10, etc.) for the DO, DI, and PWM modules.