beautypg.com

9 setting alarms and alarm indications, Setting alarms and alarm indications -54, 9 settng alarms and alarm indcatons – Yokogawa PC-Based MX100 User Manual

Page 68: Settng the alarm, Showng/hdng alarms

background image

2-54

IM MX180-01E

2.9 Settng Alarms and Alarm Indcatons

Procedure

Settng the Alarm

Rate-of-change interval

when the Type is set to

rHigh and rLow

Scroll to the right to

display alarms 1 to 4

Hysteresis of alarm 2

Alarm value of alarm 2

Alarm 2 type

Hysteresis of alarm 1

Alarm value of alarm 1

Alarm 1 type

For computation

channels

Click here

1.

Click Channel to show the Channel setup screen.

2.

Click the Meas. Channel tab or the Math Channel tab.

3.

In the Type list, select the alarm type for Alarm 1, Alarm 2, Alarm 3, or Alarm 4.

When not using difference input on measurement channels, select OFF, High, or Low. When
using difference input, select OFF, dHigh, or dLow.
On computation channels, select OFF, High, Low, rHigh, or rLow.

4.

Click the value box, and enter the alarm value.

5.

Click the Hysteresis box, and enter the alarm hysteresis value.

6.

If you selected a rate-of-change alarm rHigh or rLow for the alarm type, select the

interval used to detect the rate-of-change from the Interval of rate-ofchange alarm
list box.

Showng/Hdng Alarms

1.

Click Monitor to show the Monitor screen.

2.

Click the Alarm ON/OFF button.

Show/Hide alarm

Alarm display area

Switch the active channel