10 digital output settings, 10 digital output settings -57, 10 dgtal output settngs – Yokogawa PC-Based MX100 User Manual

Page 71: Index, Settng the dgtal output of alarms, Settng the dgtal output other than alarms

background image

2-57

IM MX180-01E

Integrat

on Mon

tor

3

2

1

4

5

App

Index

2.10 Dgtal Output Settngs

Procedure

Settng the Dgtal Output of Alarms

Alarm reference channel

Select output or not output

Turn ON/OFF Alarm 1

Select the alarm

Turn ON/OFF Alarm 4

Turn ON/OFF Alarm 3

Turn ON/OFF Alarm 2

Select hold/non-hold

of output relay

Select energize/de-energize

of output relay

1.

Click Channel to show the Channel setup screen.

2.

Click the DO Channel tab.

3.

Select the Use check boxes for the DO channels you wish to output.

4.

Click the Alarm button under Action.

5.

Click the First or Last alarm reference channel box under Ref. Ch. and enter the

measurement or computation channel numbers to reference for the alarm output.

6.

Click the Level 1, Level 2, Level 3, or Level 4 button under Ref. Ch.

7.

Click the Energize box to select an output relay action of Energize or De-energize.

8.

Click the Hold box to select an output relay behavior of Hold or Non-hold.

Settng the Dgtal Output Other Than Alarms

Select output or not output

If Action is set to Manual,

click the button from 1 to 4

Select the source action

Select hold/non-hold

of output relay

Select energize/de-energize

of output relay

4.

Click the option button under Action to select the action used as the digital output

source.

5.

If you set Action to Manual, click any of the Manual DO buttons 1 to 4.

6.

Click the Energize box to select an output relay action of Energize or De-energize.

7.

Click the Hold box to select an output relay behavior of Hold or Non-hold.