Chapter 4 specification, 1 common specifications, Common specifications -1 – Yokogawa PC-Based MX100 User Manual
Page 89: Index, Standard operating conditions, Transport and storage conditions, Mechanical specifications, Supported standards
4-1
IM MX100-01E
Specification
3
2
1
4
5
Index
Chapter 4
Specification
4.1 Common Specifications
Standard operating conditions
Operating temperature range: 0 to 50°C
Operating humidity range:
20 to 80% RH for 0 to 40°C
10 to 50% RH for 40 to 50°C
Rated supply voltage:
AC power supply, 100 to 240 VAC
Supply voltage range used: AC power supply, 90 to 250 VAC
Power supply frequency:
50 Hz ±2%, 60 Hz ±2%
Power consumption:
Up to approximately 70 VA maximum when six modules
are used
Vibration:
10 to 60 Hz 0.2m/s
2
or less
Shock:
Not allowed
Magnetic field:
400 A/m or less (50/60 Hz)
Position:
Upright and horizontal to ground
Structure:
Not explosion-proof
Usage location:
Indoors
Operating altitude:
2000 m or less
Installation category:
II (per CSA22.2 No. 61010-1)
Pollution degree:
2 (per IEC61010-1 CSA22.2 No. 61010-1)
Transport and Storage Conditions
Environmental conditions during transport and storage
Storage ambient temperature: -25 to 60°C
Storage ambient humidity:
5% to 95% RH (no condensation)
Vibration:
10 to 60 Hz 4.9m/s
2
or less
Shock:
392 m/s
2
or less (packaged condition)
Mechanical Specifications
External dimensions:
Approx. 442 Ч 131 Ч 159 mm (when six slots are attached)
Weight:
Approx. 4.1 kg (maximum total weight)
Installation method:
Desktop or floor, panel mount, or attached to a DIN rail
Material:
Steel plate, aluminum die-cast, molded plastic resin
Supported Standards
CSA:
Conforms to CSA22.2 No. 61010-1, overvoltage category II,
pollution degree 2
UL:
Conforms to UL61010B-1 (CSA NRTL/C)
CE:
EMC directives;
EN61326 Class A, EN61000-3-2,
EN61000-3-3, EN55011 Class A, Group 1
Low voltage directive: EN61010-1; measurement category II,
pollution degree 2
C-Tick:
Conforms to AS/NZS CISPR11 Class A Group1
Installation category II: An index for defining transient overvoltages (includes the rated
impulse withstand voltage, and applies to electrical equipment
supplied with power from fixed installations such as distribution
boards).
Pollution degree 2:
Indicates the degree of adherence by a solid, liquid, or vapor that
reduces the withstand voltage or surface resistance (applies only
to normal indoor atmospheres (with non-conductive pollution).
Measurement category II:
Applies to electrical instruments that are powered by wall outlets
and other fixed installations that are wired to distribution boards,
or measurements of such wires.