Output operation during abnormality (by module) – Yokogawa PC-Based MX100 User Manual
Page 42
1-33
IM MX100-01E
Explanation of Functions
3
2
1
4
5
Index
Output When Abnormal, or after Recovery from Abnormality
Output Operation during Abnormality (by Module)
Abnormal
Abnrml
Abnormal Status
Output Operation
Module
Display
Main Module
b[SQR]
*
System error
Operation upon startup
bF
Dip switches
F0
ROM error
F1
SRAM error
Operation upon startup
F2
EEPROM error
F3
Battery error
F4
Ethernet error
P[SQR]
*
CF card related error
No effect (normal operation)
None
Communication timeout error Transmission within units: no effect
(normal operation)
Transmission between units/manual
output/pattern output: operation
when error generated
C1
Comm multiple connect error No effect (normal operation per the
previously connected device)
Output Modules E0
Range information error Operation
upon startup or when
output value uncertain
E1
Calibration value error
E2
Error during calibration
Internal communication error
occurs, resulting in an error
recovery event. If the error
recovery time is 10 s or more,
output is performed per the
operation upon error occurrence,
and then output is executed per the
operation upon startup.
E3
Error in writing the calibration value.
E4
Unusable modules
Operation upon startup or when
output value uncertain
Input Modules
E0
Range information error
Operation upon errors occurrence
(except for transmission within
E1
Calibration value error
units, since the transmission
E4
Unusable modules
source input channel is illegal)
E5
Initial balance error
No effect (±Over is likely)
* [SQR] is a placeholder for the number corresponding to the error.
1.11 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output
Module