Output type, Output waveform, Pulse interval – Yokogawa PC-Based MX100 User Manual
Page 38: Output update interval, Output range, Operation when errors occur upon startup
1-29
IM MX100-01E
Explanation of Functions
3
2
1
4
5
Index
1.10 Functions of the 8-CH, Medium-Speed PWM
Output Module
This module is equipped with eight outputs that can output pulse wave duty. A duty pulse
waveform is output according to the specified pulse interval. A pulse interval can be set
for each channel.
Input terminal (clamp terminal)
Terminal cover
Output Type
Transmission output: Outputs a duty pulse waveform corresponding to the measurement
computation results of the input channel specified on the same unit.
User output:
The specified value is output based on the data sent from the PC
software. Transmission output of computation channel data or of
data from separate units is possible.
Output Waveform
Pulse interval
Output width
External
power supply
voltage
Duty=
Output width
Pulse interval
×100 [%]
Pulse Interval
1 ms to 300 s (can be set channel by channel)
However,
1 ms interval setting rng: 1 ms to 30.000 s
Can be set in units of 1 ms
10 ms interval setting rng: 10 ms to 300.00 s
Can be set in units of 10 ms
Output Update Interval
The output is updated every 100 ms (minimum). It is not synchronized to the
measurement interval.
Output Range
0.000% to 100.000%
Operation When Errors Occur upon Startup
See section 1.11.