External dimensions, Output span setting, Handling abnormal data – Yokogawa PC-Based MX100 User Manual
Page 118
4-30
IM MX100-01E
External Dimensions
Unit: mm
57
13
1
150.8
If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3
mm.
Setting Value of Span and Preset, and Specified Value of User Output
PWM output setting value
span and preset value
Specified Value of User Output
(count)
0.000%
0
20.000%
20000
40.000%
40000
60.000%
60000
80.000%
80000
100.000%
100000
Output Span Setting
Span setting data when setting transmission output
Target output [%]
0.000
50.000
100.000
PC data*
0
50000
100000
*
PC data refers to internal data between the PC and the MX100 main unit.
Handling Abnormal Data
Types of Abnormal Data
Output Values
Abnormal data upon startup
Preset value or previously held value can be selected
Data upon error occurrence
Preset value or previously held value can be selected
When input channels differ
Preset value or previously held value can be selected
+OVER
Duty 100.000% output
–OVER
Duty 0% output
±OVER determination
For command output, ±OVER determination is performed on the PC, and if the limit
value is exceeded, it is clipped at that limit value. For retransmission output, OVER is
determined by the MX100 main unit.
±OVER conditions
• When duty exceeds 0.000-100.000%
• When the input channel is ±OVER in the case of transmission output
4.11 8-CH, Medium-Speed PWM Output Module (MX120-PWM-M08) Specifications