5 power connection and on/off, Power connection and on/off -19, Index – Yokogawa PC-Based MX100 User Manual
Page 64: Warning
2-19
IM MX100-01E
Installation and W
iring
3
2
1
4
5
Index
2.5 Power Connection and ON/OFF
WARNING
• To prevent the possibility of electric shock when wiring, confirm that the power
supply source is turned OFF.
• To prevent an electric shock or fire, use only power cords supplied by
YOKOGAWA for the MX100.
• Make sure to perform protective earth grounding to prevent electric shock.
Connect the power cord for the MX100 to a three-prong power outlet with a
protective earth terminal. The AC outlet must be of a three-prong type with a
protective earth ground terminal.
Do not use the functional ground terminal (see section 2.2, “Installation”) as a
protective earth terminal.
• Do not use an extension cord without protective earth ground. Otherwise, the
protection function will be compromised.
Use a power supply that meets the conditions indicated below.
Item
Specification
Rated supply voltage
100-240 VAC rms
Supply voltage range used
AC power supply, 90 to 250 VAC rms
Rated supply voltage frequency 50/60 Hz
Allowable line frequency range
50/60 Hz ±2%
Maximum power consumption
Up to approximately 70 VA maximum when six modules are used
Note
Do not use a supply voltage in the range 132 to 180 VAC, as this may have adverse effects on
the measurement accuracy.
Connections with the Power Cord (Power Supply/Cord Basic Specification Code
1*)
* is D, F, R, Q, or H.
1.
Check that the power switch of the main module is OFF.
2.
Connect the power cord plug to the power connector of the MX100. (Use the
power cord that came with the package.)
3.
Connect the plug on the other end of the power cord to the outlet that meets the
conditions above.
Use a three-prong power outlet with a protective earth ground terminal.
Power switch
When the basic suffix code is 1D
Power
connector
3-prong outlet
Power cord
(included in the package)