1-36

IM MX100-01E

1.12 Functions of the 10-CH, Medium-Speed Digital

Output Module

This module outputs ten contact signals based on the alarm output settings and output
settings on the PC software.

Output terminal (clamp terminal)

Terminal cover

Output Type

The MX100 has the following types (output factors) are available.

Type

Description

Relay Action

Output Hold

Behavior

Alarm

Alarm output of measurement /

computation channels

Energize or deenergize

selectable

Hold

*2

or non-hold

selectable

Manual

Manual DO operation using the

software

Energize or deenergize

selectable

Fail

When a failure occurs in the

CPU of the MX100 main module

Normal: Energized

Failure: Deenergized

Error

Output when an error

*1

is

detected in the MX100

Energize or deenergize

selectable

Hold

*2

or non-hold

selectable

*1 Below are the errors that can occur in the MX100.

• A data output request timeout (60 s) occurs while recording data. (except when the /DS

option functions are enabled)

• An input module detected at power-on that is able to make measurements is removed.
• A module breaks down.
• An unidentifiable module is attached.

*2 Holds the output until the PC software issues the output release command (relay ACK).

Output Update Interval

The output is updated every 100 ms (minimum). It is not synchronized to the
measurement interval.

Relay Action and Hold Behavior

You can select whether to energize or de-energize the output relay when outputting
contact signals on the PC software. You can also select whether the output relay is
turned OFF (non-hold) or kept ON (hold) until an output release command is received.

Output cause

occurrence

• When set to non-hold

• When set to hold

Relay output ON

Relay output OFF

Relay ACK

Relay output ON

Relay output OFF

Output cause

occurrence