Steady output operation, Steady output operation -32, Output operation while communication is connected – Yokogawa PC-Based MX100 User Manual
Page 41
1-32
IM MX100-01E
Steady Output Operation
Output Operation While Communication Is Connected
Communication Connection Status
Output Operation
Comm. connects (initial connection after power ON)
Operation upon startup
Comm. connects
Holds the output value (last output value)
(disconnected and restored for the 2nd or more time)
Communication disconnected normally
Holds the output value (last output value)
Output Operation according to the Measurement Status and Transmission
Output Status
Transmission output in the table is ON when Transmission output is selected in the
Action menu of the MX100 Standard Software, or when DAQMXTRANSMIT_RUN is
executed in the MX100/DARWIN API. Transmission output in the table is OFF when
Transmission output is cleared in the Action menu of the MX100 Standard Software, or
when DAQMXTRANSMIT_STOP is executed in the MX100/DARWIN API.
Output Setting Status
Output Operation
Trans. output
Meas stop → meas. start
Starts trans. output/holds within
within units
units output value (depends on
trans. output execution on/off )
on: transmission output starts
off: holds output value
Measuring → meas. stop
Holds output value
(last output value)
Meas stopping Trans. output exec. on* → off* Holds output val. (no change.)
Trans. output exec on → off
Holds output val. (no change.)
Measuring
Trans. output exec off → on
Starts trans. output
Trans. output exec on → off
Holds output val. (last val.)
Trans. output
Meas stop → meas start
Starts user output or holds
between units
output value (depends on trans
(user output)
output exec. on/off status)
on: transmission output starts
off: output value held
Measuring → meas stop
Holds output value
(last output value)
Meas stopping Trans. output exec off → on
Holds output val. (no change.)
Trans. output exec on → off
Holds output val. (no change.)
Measuring
Trans. output exec off → on
User output
Trans. output exec on → off
Holds output val. (last output value)
Manual output
Meas stop → meas start
No effect
(user output)
Measuring → meas stop
No effect
Meas stopping Trans. output exec off → on
No effect
Trans. output exec on → off
No effect
Measuring
Trans. output exec off → on
No effect
Trans. output exec on → off
No effect
Pattern output
Meas stop → meas start
No effect
(user output)
Measuring → meas stop
No effect
Meas stopping Trans. output exec off → on
No effect
Trans. output exec on → off
No effect
Measuring
Trans. output exec off → on
No effect
Trans. output exec on → off
No effect
* on: enabled off: disabled
Transmission output execute enabled: when “Transmit” under the Action menu of the PC
software is selected
Transmission output execute disabled: when “Transmit” under the Action menu of the PC
software is not selected
1.11 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output