The MX100 can be detected using the Search button, but connection fails.

Probable Cause

Corrective Action

Ref. Page

The IP address is set to the default value.

The default value cannot be used to make the

connection.

Set the correct IP address.

*

There is a problem in the network

configuration.

Check that the IP address, subnet mask, and default gateway

settings of the PC and the MX100 settings are correct.

*

The PC software, main module style number,

and release number rule is not upheld.

Check the PC software release number and main module style

number before upgrading the version.

[PC software release no.] ≥ [main module style no.]

i

*

See the MX100 Standard Software User’s Manual (IM MX180-01E).

The Calibrator cannot connect to the MX100.

Probable Cause

Corrective Action

Ref. Page

Attempting to make multiple connections.

Another software program such as the MX100

Standard Software is already connected.

Close all other software programs such as the MX100 Standard

Software.

*

The main module and input/output module

style number rule is not upheld.

Check the release number of the PC software and the main

module style number, then upgrade the version.

[PC software release no.] ≥ [main module style no.] ≥ [input/output

module style no.]

i

*

See the MX100 Standard Software User’s Manual (IM MX180-01E).

The connected input/output module is not detected.

Probable Cause

Corrective Action

Ref. Page

Module connection or module startup error.

Attached the module while the power was ON.

Turn OFF the power. Detach the input/output module once and

attach it again.

2-4, 2-19

The PC software, main module, and input/

output module style and release number rule

is not upheld.

Check the PC software release number and main module style

number before upgrading the version.

[PC software release no.] ≥ [main module style no.] ≥ [input/output

module style no.]

i

Carried out an incorrect calibration.

Recalibrate.

*

The 10-CH, Pulse Input Module (MX114-

PLS-M10) is connected.

The 10-CH, Pulse Input Module cannot be used with the MX100.

Use this module with the MW100.

1-5

*

See the MX100 Standard Software User’s Manual (IM MX180-01E).