Medium speed pwm output module (mx120) -32, Specifications regarding settings (by module) – Yokogawa PC-Based MX100 User Manual
Page 120
4-32
IM MX100-01E
4.12 Specifications Common to the 8-CH Medium-
Speed Analog Output Module and the 8-CH
Medium Speed PWM Output Module (MX120)
Specifications Regarding Settings (by Module)
Set Channels
(Module)
Setting Contents
Setting Note
Output
channels
(AO, PWM)
Span setting
range
AO (V)
–10.000 to 10.000 V
-
-
AO (mA)
0.000 to 20.000 mA
PWM
0.000 to 100.000%
Preset value
setting range
AO (V)
–11.000 to 11.000 V
-
-
AO (mA)
0.000 to 22.000 mA
PWM
0.000 to 100.000%
Setting span (minimum, maximum) specified in reverse
Y
-
Setting span (minimum, maximum) specified as the same
No
-
Computation
Channels
Reading of in
equations
Transmission output channels within units
No
-
Transmission output channels between
units
No
-
Manual output channel
Y
Depending
on function
dedicated
Pattern output channel
Y
Specifications Regarding Settings Changes (Automatic Setting upon Change
Event)
When a setting change occurs, transmission output on all channels specified for
transmission output within units is set from disabled to enabled. This operation is
performed even if the channel whose setting was changed is not a transmission output
channel.
Overview of Output Operation When Setting Holding of Previous Value of
Transmission Output
Measurement
start
Measurement
stop
(or Transmission output
execute disabled)
Measurement
restarts
(or Transmission output
execute enabled)
Previous value
(held)
Power ON
Output value
Value held