Wiring the analog output modules, Wiring the pwm output modules, Index wiring the analog output modules – Yokogawa PC-Based MX100 User Manual
Page 62: Caution
2-17
IM MX100-01E
Installation and W
iring
3
2
1
4
5
Index
Wiring the Analog Output Modules
External power supply
Voltage
V+
Load
+ 24 V
power supply
(when using current output)
Direction of
current
Vext
Current
I+
Load
CAUTION
Two power supply terminals are connected internally. Therefore, do not connect a
separate external power supply to them as fire can result.
Main Output Specifications
Terminal type:
Clamp, attached and removed in units of 4 channels
Load impedance:
Voltage 5 kΩ or more
Current 600 Ω or less
Applicable wire size: 0.08 to 2.5 mm
2
(AWG28 to 12)
Wiring the PWM Output Modules
External power supply
Pulse width output
V+
Load
+
4-28 V
power supply
CAUTION
Two power supply terminals are connected internally. Therefore, do not connect a
separate external power supply to them as fire can result.
Main Output Specifications
Output capacity:
1A/ch max, however, 4 A or less total for all modules
*1, *2
Terminal type:
Clamp, attached and removed in units of 4 channels
Applicable wire size: 0.08 to 2.5 mm
2
(AWG28 to 12)
*1 A 1A current limit circuit is built in to the output circuit. Once the current limit circuit is ON,
the circuit continues to operate unless the external power supply is turned OFF.
*2 This module has a built-in fuse. The built-in fuse protects against fires or abnormal
emissions of heat due to load short-circuiting or other abnormalities.
2.4 Connecting the Signal Wires