Index – Yokogawa PC-Based MX100 User Manual
Page 44
1-35
IM MX100-01E
Explanation of Functions
3
2
1
4
5
Index
Output Operation after Recovery from Abnormality (by Output Setting)
Output Setting
Abnormality Recovery
Output Operation
Trans. output
Referenced input module recovers
Operation upon errors →
within units
(removed input modules are inserted) transmission output
Referenced input channel changed
from Skip to measurement range
Referenced input channel is Invalid
Recovers to normal from (math error
in difference computation)
Recover after communication timeout No effect
Recover after internal comm error
If the error recovery time is 10 s or
more; operation upon error
occurrence → operation upon
startup -> transmission output
If the error recovery time is within
10 s; operation upon startup →
transmission output
CPU abnormality (does not recover)
Operation upon errors
Trans. output
Referenced input module recovers
Operation upon errors (per PC
between units
(removed input modules are inserted) software → user output
*1
(user output)
Referenced input channel changed
from Skip to measurement range.
*2
Referenced channel is invalid; recovers
to normal value from (math error).
Recover after communication timeout Operation upon errors → user output
*1
Recover after internal comm error
If the error recovery time is 10 s or
more; operation upon error
occurrence → operation upon
startup → user output
*1
If the error recovery time is within
10 s, Operation upon startup →
user output
*1
CPU abnormality (does not recover)
Operation upon errors
Manual output
Recover after communication timeout. Operation upon errors → user output
*1
(user output)
Recover after internal comm error
If the error recovery time is 10 s or
more, Operation upon errors
→ operation upon startup → user
output
*1
If the error recovery time is within
10 s, Operation upon startup →
user output
*1
CPU abnormality (does not recover)
Operation upon errors
Pattern output
Recover after communication timeout Operation upon errors → user output
*1
(user output)
Recover after internal comm error
If the error recovery time is 10 s or
more; operation error occurrence →
operation upon startup → user output
*1
If the error recovery time is within
10 s, Operation upon startup →
user output
*1
CPU abnormality (does not recover)
Operation upon errors
*1 Executes the user output from the PC software after recovery from errors.
*2 Invalid with the MX100 Standard Software. With the API for MX100 and DARWIN, it is “Skip.”
1.11 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output