1.5 Functions of the 30-CH, Medium-Speed DCV/

TC/DI Input Module

This module is equipped with 30 inputs and measures DC voltage, Thermocouple, and
digital input (DI) at a minimum measurement interval of 500 ms.
It takes up three modules worth of space when attaching to the base plate.

Terminal

cover

Input terminal

(clamp terminal)

Terminal

cover

Input terminal

(M3 screw terminal)

MX110-VTD-L30/H3

MX110-VTD-L30

Input Type and Measurement Range

The following measurements are possible.

Input

Measurement Range Type

Rated Measurement Range

DC voltage

20 mV

–20.000 to 20.000 mV

60 mV

–60.00 to 60.00 mV

200 mV

–200.00 to 200.00 mV

2 V

–2.0000 to 2.0000 V

6 V

–6.000 to 6.000 V

20 V

–20.000 to 20.000 V

100 V

–100.00 to 100.00 V

Thermocouple

R

0.0 to 1760.0°C

S
B

0.0 to 1820.0°C

K

–200.0 to 1370.0°C

E

–200.0 to 800.0°C

J

–200.0 to 1100.0°C

T

–200.0 to 400.0°C

N

0.0 to 1300.0°C

W

0.0 to 2315.0°C

L

–200.0 to 900.0°C

U

–200.0 to 400.0°C

KPvsAu7Fe

0.0 to 300.0K

DI

Level

Vth = 2.4 V

Contact input

ON: 1 kΩ or less,

OFF: 100 kΩ or more

(parallel capacitance: 0.01 µF

or less)