3.10 Countng Pulses (/PM1 opton)

• Example 1: Pulse Sum

Display the sum of the pulses from pulse input terminal 6.

Number of pulses

per scan interval

TLOG.SUM

Pulse sum value

Pulse input

Scan interval

Time

(Sum)

P6

Calculaton Expresson

Select the channel and set the calculation expression. Set an appropriate

Span

Lower, Span Upper, and Unt.

Channel

Calculaton Expresson

Descrpton

101

TLOG.SUM(P6)

The sum of the number of pulses in each scan

interval.

• Example 2: Pulses Per Mnute

Using the MV2008 (scan interval 250 ms), count the number of pulses received by

pulse input terminal 6, and calculate the number of pulses per minute.

Number of pulses

per second

101ch

102ch

Number of pulses

per minute

Pulse input

Sampling interval

(250 ms)

Time

(Moving average over a minute)

(60x)

Calculaton Expresson

This table shows which calculation expressions to assign to which channels. Set an

appropriate

Span Lower, Span Upper, and Unt.

Channel

Calculaton Expresson

Descrpton

101

Q6

Number of pulses per second

102

101*K01

Number of pulses per minute

Constant Value

Descrpton

K01

60

The coefficient for converting pulses per

second to pulses per minute.

Channel

Rollng Average

Descrpton

101

Interval: 1 s

Moving average over a minute

Number of samples: 60

Channel

Computation starts with the smallest channel number at every scan interval.
Assign larger channel numbers to computation channels that calculate pulses per

minute than you assign to computation channels that calculate pulses per second.