3-20

IM MV1000-01E

3.11 Settng Range-Out Detecton for Lnearly

Scaled Measurement Channels

Dsplay

MV1000

Press

MENU > then select Menu tab > Basc settng mode > Envronment tab > Input,

Alarm

MV2000

Press

MENU and then select Menu tab > Basc settng mode > Envronment tab >

Vew, Message, Input, Alarm.

Settngs

• Input > Value on over-range

Settng

Descrpton

Free

Ignoring the decimal point, less than –30000 is a negative range-out, and above

30000 is a positive range-out. They are displayed as –Over and +Over.

Over

A value less than –5% of the scale is a negative range-out, and a value greater than

105% of the scale is a positive range-out. They are displayed as –Over and +Over.
Example: If the scale is 0.0 to 200.0, a value less than –10.0 is a negative range-

out, and a value greater than 210.0 is a positive range-out.

Note

With computation and report functions such as TLOG and CLOG, you can specify how the MV
will handle scale range out values.

See section 10.1.