Yokogawa Button Operated MV2000 User Manual
Page 100
3-20
IM MV1000-01E
3.11 Settng Range-Out Detecton for Lnearly
Scaled Measurement Channels
Dsplay
MV1000
Press
MENU > then select Menu tab > Basc settng mode > Envronment tab > Input,
Alarm
MV2000
Press
MENU and then select Menu tab > Basc settng mode > Envronment tab >
Vew, Message, Input, Alarm.
Settngs
• Input > Value on over-range
Settng
Descrpton
Free
Ignoring the decimal point, less than –30000 is a negative range-out, and above
30000 is a positive range-out. They are displayed as –Over and +Over.
Over
A value less than –5% of the scale is a negative range-out, and a value greater than
105% of the scale is a positive range-out. They are displayed as –Over and +Over.
Example: If the scale is 0.0 to 200.0, a value less than –10.0 is a negative range-
out, and a value greater than 210.0 is a positive range-out.
Note
With computation and report functions such as TLOG and CLOG, you can specify how the MV
will handle scale range out values.
See section 10.1.