beautypg.com

Yokogawa Button Operated MV2000 User Manual

Page 82

background image

3-2

IM MV1000-01E

3.2 Settng Burnout and Reference Juncton

Compensaton

This section explains how to set the function that detects sensor burnouts in
thermocouple and 1-5V inputs as well as how to set the reference junction compensation
method of the thermocouple.

Dsplay

Press

MENU then select Menu tab > Basc settng mode > Menu tab > Burnout, RJC.

Settngs

• Frst-CH, Last-CH

Select the target channels.

• Burnout > Mode

Detects thermocouple and 1-5V input sensor burnouts.

Settng

Descrpton

Off

Does not detect sensor burnouts.

Up

When the MV detects a burnout, it sets the measured result to “+Over.” The

measured value is displayed as “Burnout.”
For 1-5V input, the MV detects a sensor burnout when the measured value exceeds

the scale upper limit by 10% of the scale width. (Example: With a scale of 0 to 100,

burnout is detected at values above 110.)

Down

When the MV detects a burnout, it sets the measured result to “–Over.” The

measured value is displayed as “Burnout.”
For 1-5V input, the MV detects a sensor burnout when the measured value goes

below the scale lower limit by 5% of the scale width. (Example: With a scale of 0 to

100, burnout is detected at values below –5.)

• RJC > Mode

Select either Internal or External as the thermocouple input reference junction

compensation method.

Settng

Descrpton

Internal

Uses the MV reference junction compensation function.

External

Uses an external reference junction compensation function. When the method is set

to External, the Volt setting is displayed.

• RJC > Volt

If you set Mode to External, enter the compensation voltage.

Settng

Descrpton

Voltage

The compensation voltage that is added to the input. Set the value in the range of

–20000 μV to 20000 μV.

This manual is related to the following products: