1-29

IM MV1000-01E

Feature Overv

ew

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

• Event Data Recordng Condtons

Item

Descrpton

Channel type

Same as with display data.

Sampling interval

Choices are available in the range of 25 ms to 600 s. However, you

cannot choose an interval that is faster than the scan interval.

File generation

A file is generated when the set data length is reached.
Files are also generated in these cases:
• When you generate a file manually.
• When there is a memory stop.
• When a file is generated using the event action function.
• After recovering from a power failure.

Modes

Recording varies depending on the mode. The following modes are

available:
Free
Pressing START/STOP starts recording. Pressing START/STOP again

stops recording.

Time

File

File

File

Adding data

Sngle
Pressing START/STOP puts the MV into a trigger-wait state. After a

trigger event occurs, the MV will record data for the set time (

Data

length). The MV will not record again even if a trigger occurs afterwards.

Time

File

Trigger condition met

Repeat
Pressing START/STOP puts the MV into a trigger-wait state. After a

trigger event occurs, the MV will record data for the set time (

Data

length). After that, the MV will return to a trigger-wait state and will

record data for the set time (

Data length) whenever a trigger event

occurs. To stop the recording of event data, press START/STOP again.

Time

File

File

Trigger condition met

Trigger condition met

Event Data Pre-trgger

The event data pre-trigger can be configured for use with triggers.
It is a function that records the data before a trigger event as event data. It is useful for

when you want to record the data before the occurrence of an alarm or other event.

The pre-trigger is set as a percentage of the event data recording time (data length).

You can set it to 0, 5, 25, 50, 75, 95, or 100%. If you set the pre-trigger to 0%, the MV
will only record the data after the trigger event.

Time

Trigger condition met

Pre-trigger data

Post-trigger data

Event Data Recordng Start Trggers

You can configure a variety of conditions as triggers for starting event data recording.
Example: Key operations, alarm occurrence, time, remote control

1.5 Data Storage Functons

This manual is related to the following products: