13.1 Sgnal Input and Alarm
Sgnal Input
Item
Specfcatons
Number of inputs, scan interval, and A/D integration time
25 ms
125 ms
4
8
6
12
24
8
10
20
30
40
48
Fast sampling mode*
Normal mode
Number of Inputs:
Model
Scan Interval
A/D Converter Integration Time
100 ms
60 Hz/50 Hz
600 Hz (fixed)
125 ms, 250 ms
1 s, 2 s, 5 s
25 ms
125 ms
125 ms, 250 ms
1 s, 2 s, 5 s
2 s, 5 s
2 s, 5 s
MV1004
MV1008
MV1006
MV1012
MV1024
MV2008
MV2010
MV2020
MV2030
MV2040
MV2048
* Not available on models equipped with external input channels (/MC1 option).
Input types
DC voltage, 1-5V, thermocouple (TC), resistance temperature detector (RTD), ON/OFF input
(DI), and DC current (by adding an external shunt resistor)
Input format
Floating unbalanced input
Measurement range and measurable range
DC voltage
20 mV
–20.000 to 20.000 mV
60 mV
–60.00 to 60.00 mV
200 mV
–200.00 to 200.00 mV
2 V
–2.0000 to 2.0000 V
6 V
–6.000 to 6.000 V
20 V
–20.000 to 20.000 V
50 V
–50.00 to 50.00 V
1-5V
1-5 V
6
0.800 to 5.200 V
Thermocouple R
1
0.0 to 1760.0°C
S
1
0.0 to 1760.0°C
B
1
0.0 to 1820.0°C
K
1
–200.0 to 1370.0°C
E
1
–200.0 to 800.0°C
J
1
–200.0 to 1100.0°C
T
1
–200.0 to 400.0°C
N
1
0.0 to 1300.0°C
W
2
0.0 to 2315.0°C
L
3
–200.0 to 900.0°C
U
3
–200.0 to 400.0°C
WRe
4
0.0 to 2400.0°C
RTD
Pt (Pt100)
5
–200.0 to 600.0°C
JPt (JPt100)
5
–200.0 to 550.0°C
DI
Voltage
0: Less than 2.4 V. 1: 2.4 V or higher (judged at the 6 V range)
Contact
7
0: Open. 1: Closed (parallel capacitance of 0.01 µF or less)
1: R, S, B, K, E, J, T, N: IEC584-1 (1995), DIN IEC584, JIS C1602-1995
2: W: W-5%Re/W-26%Re (Hoskins Mfg. Co.), ASTM E988
3: L: Fe-CuNi, DIN43710, U: Cu-CuNi, DIN43710
4: WRe: W-3%Re/W-25%Re (Hoskins Mfg. Co.)
5: Pt100: JIS C1604-1997, IEC751-1995, DIN IEC751-1996
JPt100: JIS C1604-1989, JIS C1606-1989
Measuring current: i = 1mA (Pt100, JPt100)
6: The range for linear scaling of 1-5V inputs. Burnout detection and low-cut functions are
available.
7:
The detected current value is approx. 10 μA.
32 to 3200°F
32 to 3200°F
32 to 3308°F
–328 to 2498°F
–328.0 to 1472.0°F
–328.0 to 2012.0°F
–328.0 to 752.0°F
32 to 2372°F
32 to 4199°F
–328.0 to 1652.0°F
–328.0 to 752.0°F
32 to 4352°F
–328.0 to 1112.0°F
–328.0 to 1022.0°F
Measurable Range
Range