beautypg.com

Dgtal dsplay, Alarm dsplay – Yokogawa Button Operated MV2000 User Manual

Page 23

background image

1-14

IM MV1000-01E

Dgtal Dsplay

Displays measured data using large numeric symbols.

For operating instructions, see section 5.2.

Unit

Tag name or channel number

Alarm mark

Measured value

Note

• Measurement Channel Numerc Value Dsplay
When the MV detects a range-out (see below), the display is either “+Over” or “-Over.”

When the MV detects a burnout on a channel that has been set to be checked for burnouts,
the display is “Burnout”. All other values are displayed numerically.
Range-outs are detected on measurement channels in the following circumstances.
• If the DC voltage input value goes above the measurable range ± 5%, a range-out is

detected. For example, when the measurement range is 2 V, the measurable range is
–2.000 to 2.000 V. If the voltage exceeds 2.200 V, a positive range-out is detected. If it
goes below –2.200 V, a negative range-out is detected.

• If the input type is thermocouple or RTD, a range-out is detected when the temperature

goes 10°C above or below the measurable range. For example, when the measurement
range is set to R, the measurable range is 0.0 to 1760.0°C. If the temperature exceeds
1770.0°C, “+Over” will be displayed. If the temperature goes below -10.0°C, “-Over” will
be displayed.

• On channels that use linear scaling, the range-out values, ignoring the decimal point,

are above 30000 and below –30000. However, you can also set the range-out values to
105% or greater, and –5% or less of the scale width, as long as those values fall within
±30000.

For configuration instructions, see section 3.11.

• Computaton Channel Numerc Value Dsplay

See section 1.9.

• External Input Channel Numerc Value Dsplay (/MC1 opton)
The range of displayable values, ignoring the decimal point, is –30000 to 30000. The

decimal place is determined by the location of the decimal point on the external input
channel’s minimum span value. Regardless of maximum and minimum span value settings,
all values within the range of –30000 to 30000 will be displayed. If the value exceeds 30000,
“+Over” will be displayed. If the value goes below –30000, “-Over” will be displayed.

• Alarm Dsplay

The alarm mark and measured values are displayed in the following ways depending

on the alarm condition.

Alarm

Release

AlarmACK

AlarmACK

Occurrence

Indication not held

Indication held

Red

Blue

Red

Blue

Red

Red

Blue

Blue

Blue

Blue

Blue

Measured

value

Blinking

red

Blinking

green

Blinking

red

Green

Red

Red

Green

Green

Green

Green

Green

Alarm mark

1.4 Dsplay

This manual is related to the following products: