Range > type, Range > range, Range > span lower,span upper – Yokogawa Button Operated MV2000 User Manual

Page 84: Range > scale lower, scale upper

background image

3-4

IM MV1000-01E

• Range > Type

Input type when Mode is set to Delta or Scale. See the explanation of Mode.

• Range > Range

These are specific input settings.

Settng

Input Type

Note

Settng Input Type

Note

20mV

–20,000 mV to 20.000 mVDC Standard

R

Type R

Standard

60mV

–60.00 mV to 60.00 mVDC

S

Type S

200mV

–200.00 mV to 200.00 mVDC

B

Type B

2V

–2.0000 V to 2.0000 VDC

K

Type K

6V

–6.000 V to 6.000 VDC

E

Type E

20V

–20.000 V to 20.000 VDC

J

Type J

50V

–50.00 V to 50.00 VDC

T

Type T

Pt

Pt100

N

Type N

JPt

JPt100

W

Type W

Level

ON/OFF (Voltage)

L

Type L

Contact

ON/OFF (Contact)

U

Type U

1-5V

0.800 V to 5.200 V

WRe

Type WRe

Settng

Input Type

Note

Settng Input Type

Note

K

Kp vs Au7Fe

/N3 option

Cu1

Cu10 (GE)

/N1 option

PLATI

PLATINEL

Cu2

Cu10 (L&N)

PR

PR40-20

Cu3

Cu10 (WEED)

NiMo

NiNiMo

Cu4

Cu10 (BAILEY)

W/WRe

W/WRe26

Cu5

Cu10: a = 0.00392 at 20°C

N2

Type N (AWG14)

Cu6

Cu10: a = 0.00393 at 20°C

Pt50

Pt50

Cu25

Cu25: a = 0.00425 at 0°C

Ni1

Ni100 (SAMA)

Ni2

Ni100 (DIN)

Ni3

Ni120

J263

J263*B

Cu53

Cu53

Cu100

Cu100: a = 0.00425 at 0°C

Pt25

Pt25

• Range > Span Lower,Span Upper

The input range. The range of available settings will be displayed on the screen.

Note

• You cannot set Span Lower and Span Upper to the same value.
• When Mode is set to 1-5V or Sqrt, you can only set Span Lower to a value that is less than

Span Upper.

• Range > Scale Lower, Scale Upper

The input range after unit conversion.
You can set the scale values to anywhere from –30000 to 30000. The decimal place is

determined by the Scale Lower setting. It can be set to the following positions: X.XXXX,
XX.XXX, XXX.XX, XXXX.X, or XXXXX.

Note

• The MV converts the measured value to a value within the range set by the Scale Lower

and Scale Upper values with their decimal points removed. For example, if you set the scale
range to –5 to 5, the range of converted values will be 10, but if you set the scale range to –5.0
to 5.0, the range of converted values will be 100. The resolution of values converted within
the range of 10 will be less than that of values converted within the range of 100. For a clear
view, set the scale values so that the range of converted values is greater than 100.

• You cannot set Scale Lower and Scale Upper to the same value.
• When Mode is set to 1-5V or Sqrt, you can only set Scale Lower to a value that is less than

Scale Upper.

3.3 Settng the Input Range