Range > type, Range > range, Range > span lower,span upper – Yokogawa Button Operated MV2000 User Manual
Page 84: Range > scale lower, scale upper
3-4
IM MV1000-01E
• Range > Type
Input type when Mode is set to Delta or Scale. See the explanation of Mode.
• Range > Range
These are specific input settings.
Settng
Input Type
Note
Settng Input Type
Note
20mV
–20,000 mV to 20.000 mVDC Standard
R
Type R
Standard
60mV
–60.00 mV to 60.00 mVDC
S
Type S
200mV
–200.00 mV to 200.00 mVDC
B
Type B
2V
–2.0000 V to 2.0000 VDC
K
Type K
6V
–6.000 V to 6.000 VDC
E
Type E
20V
–20.000 V to 20.000 VDC
J
Type J
50V
–50.00 V to 50.00 VDC
T
Type T
Pt
Pt100
N
Type N
JPt
JPt100
W
Type W
Level
ON/OFF (Voltage)
L
Type L
Contact
ON/OFF (Contact)
U
Type U
1-5V
0.800 V to 5.200 V
WRe
Type WRe
Settng
Input Type
Note
Settng Input Type
Note
K
Kp vs Au7Fe
/N3 option
Cu1
Cu10 (GE)
/N1 option
PLATI
PLATINEL
Cu2
Cu10 (L&N)
PR
PR40-20
Cu3
Cu10 (WEED)
NiMo
NiNiMo
Cu4
Cu10 (BAILEY)
W/WRe
W/WRe26
Cu5
Cu10: a = 0.00392 at 20°C
N2
Type N (AWG14)
Cu6
Cu10: a = 0.00393 at 20°C
Pt50
Pt50
Cu25
Cu25: a = 0.00425 at 0°C
Ni1
Ni100 (SAMA)
Ni2
Ni100 (DIN)
Ni3
Ni120
J263
J263*B
Cu53
Cu53
Cu100
Cu100: a = 0.00425 at 0°C
Pt25
Pt25
• Range > Span Lower,Span Upper
The input range. The range of available settings will be displayed on the screen.
Note
• You cannot set Span Lower and Span Upper to the same value.
• When Mode is set to 1-5V or Sqrt, you can only set Span Lower to a value that is less than
Span Upper.
• Range > Scale Lower, Scale Upper
The input range after unit conversion.
You can set the scale values to anywhere from –30000 to 30000. The decimal place is
determined by the Scale Lower setting. It can be set to the following positions: X.XXXX,
XX.XXX, XXX.XX, XXXX.X, or XXXXX.
Note
• The MV converts the measured value to a value within the range set by the Scale Lower
and Scale Upper values with their decimal points removed. For example, if you set the scale
range to –5 to 5, the range of converted values will be 10, but if you set the scale range to –5.0
to 5.0, the range of converted values will be 100. The resolution of values converted within
the range of 10 will be less than that of values converted within the range of 100. For a clear
view, set the scale values so that the range of converted values is greater than 100.
• You cannot set Scale Lower and Scale Upper to the same value.
• When Mode is set to 1-5V or Sqrt, you can only set Scale Lower to a value that is less than
Scale Upper.
3.3 Settng the Input Range