4-2
IM MV1000-01E
• Event Data Recordng Condtons
Press MENU and then select > Menu tab > Data save > Event data.
Settngs
• Memory > Data Knd
Settng
Descrpton
Display
Records display data.
E+D
Records display data and event data. You cannot select this setting if the
trend interval switching function (Trend rate switching) is set to on On (see
section 6.3 for details)
Event
Records event data.
• Memory sample > On/Off
Select
On for the target channels.
• Dsp data > Trend/Storage nterval
Set the display trend/storage interval. For the trend/storage intervals that can only be
set on high-speed input models, 5 s/div and 10 s/div, 1 division (div) is equal to 40
dots.
You can only set trend/storage intervals that are longer than the scan interval you set
in Basic Setting Mode.
• Dsp data > Save nterval (when recordng dsplay data)
Set the size of recorded data files. Recorded data is divided into files of the size
specified here. The values that you can set here vary depending on the Trend/Storage
interval setting.
Trend/Storage
nterval
1
5s
2
10s
2
15s
3
30s
1mn
Samplng nterval
125ms
250ms
500ms
1s
2s
Selectable Save
Interval Values
10 min to 12 h
10 min to 1
day
10 min to 3
days
10 min to 7
days
10 min to 14
days
Trend/Storage
nterval
1
2mn
5mn
10mn
15mn
20mn
Samplng nterval
4s
10s
20s
30s
40s
Selectable Save
Interval Values
10 min to 14
days
10 min to 31
days
10 min to 31
days
10 min to 31
days
1 h to 31 days
Trend/Storage
nterval
1
30mn
1h
2h
4h
10h
Samplng nterval
1 min
2 min
4 min
8 min
20 min
Selectable Save
Interval Values
1 h to 31 days
1 h to 31 days
2 h to 31 days
4 h to 31 days
8 h to 31 days
1 You can only set a data interval that corresponds to a sampling interval that is slower than
the scan interval.
2 Only available on high-speed input models of the MV.
3 Selectable in fast sampling mode on medium-speed input models of the MV.