Yokogawa Button Operated MV2000 User Manual
Page 47
1-38
IM MV1000-01E
About TmerReset
If Event is set to Relay, Switch, MatchTimeTimer, or Alarm, TimerReset will not result
in a timeout (an action will not be executed even if the timer is used as an event).
If Event is set to Remote or UserKey, a timeout will occur (if the timer is used as an
event, an action will be executed).
About PanelLoad
PanelLoad can only be specified as an action when Event is set to Remote.
PanelLoad loads a setup data file, LOAD1.PDL, LOAD2.PDL, or LOAD3.PDL, in
the root directory of the CF card onto the MV, and uses it to configure the MV. Only
settings that pertain to Setting Mode are updated.
You must create a setup file and save it to the CF card in advance.
Event Trgger Operaton
When Event is set to Relay, Switch, or Alarm:
The Trigger action will always occur when an output relay is activated, when an
internal switch is set to 1, or when an alarm occurs. However, the number of times the
trigger is activated depends on the event data mode (Single or Repeat).
About TmeAdjust
TimeAdjust can only be specified as an action when Event is set to Remote.
TimeAdjust sets the MV internal clock to the closest hour.
• Operaton When the MV s Not Memory Samplng
Dfference from the Nearest Hour Operaton
0 s to 1 min 59 s
Truncates the minutes and seconds.
Example: 10 hours 01 min 50 s becomes 10 hours 00
min 00 s.
2 min to 57 min 59 s
The time is not changed.
58 min to 59 min 59 s
Rounds up the minutes and seconds.
Example: 10 hours 59 min 50 s becomes 11 hours 00
min 00 s.
• Operaton When the MV s Memory Samplng (See secton 1.11 for
detals.)
If the time difference between the time when the remote control signal is applied
and the nearest hour is within the preset time, the time is gradually corrected.
Otherwise, the time is corrected immediately.
1.7 Event Acton Functon