beautypg.com

Yokogawa Button Operated MV2000 User Manual

Page 69

background image

2-9

IM MV1000-01E

Installat

on and W

rng

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Wrng Procedure

As shown in the figure below, the optional terminal block is located on the rear panel. The
MV is only equipped with an optional terminal block when an option that requires input/
output, such as the alarm output relay (/A options), FAIL/status output relay (/F1 option),
and remote control function (/R1 option), is installed . There is a terminal cover screwed
onto the optional terminal block. It has a label indicating the terminal arrangement on it.

1.

Turn OFF the MV and remove the terminal cover.

2.

Connect the signal wires to the terminals.

The recommended torque for tightening the

screws is 0.9 to 1.0

N•m.

3.

Replace the terminal cover and fasten it with screws. The appropriate tightening

torque for the screws is 0.6 N•m.

Optonal Termnal Arrangement

Locaton of the Optonal Termnal Blocks

• MV1000

Optional terminal

block 1

• MV2000

Optional terminal

block 1

Optional terminal

block 2

2.3 Optonal Termnal Wrng

This manual is related to the following products: