beautypg.com

Yokogawa Button Operated MV2000 User Manual

Page 21

background image

1-12

IM MV1000-01E

• Waveform Updatng

Every 30 dots makes up one division (also referred to as DIV) on the time axis.

The waveform update interval is the time corresponding to one dot. The time

corresponding to one dot depends on the time set to one division (the trend interval).

The relationship between the trend interval and the speed of waveform movement in

the display is as follows:

Trend nterval (per DIV)

5 s

1

10 s

1

15 s

2

30 s

1 mn

Tme correspondng to one dot (n seconds)

0.125

0.25

0.5

1

2

Speed of waveform movement (approxmaton n mm/h) 10000

5000

2500

1250

625

Trend nterval (per DIV)

2 mn

5 mn 10 mn 15 mn 20 mn

Tme correspondng to one dot (n seconds)

4

10

20

30

40

Speed of waveform movement (approxmaton n mm/h) 312

156

78

42

31

Trend nterval (per DIV)

30 mn

1 h

2 h

4 h

10 h

Tme correspondng to one dot (n seconds)

60

120

240

480

1200

Speed of waveform movement (approxmaton n mm/h) 21

10

5.2

2.6

1.0

1 40 dots per division. Available on high-speed input models of the MV.
2 Available on medium-speed input models of the MV when in fast sampling mode .

Swtchng Trend Intervals

(For instructions on how to set the second interval, see

section 6.3.)

You can press T/DIV to change the trend interval. You can also switch from the

ordinary trend interval to the secondary trend interval, and vice versa, while the MV is

collecting data.

• Wrtng Messages

Trend display

Preset messages

Free messages

You can enter non-preset messages.

1

2

3

4

Start

Material 1

Preset Messages

(For configuration and operating instructions, see section 6.4.)

You can choose preset messages to be written on the waveform.

Max. number of messages: 100 (Messages 1 through 10 are free messages.)

Free Messages

(For configuration and operating instructions, see section 6.4.)

You can enter non-preset messages.

Max. number of free messages: 10

Automatcally wrtten messages (For configuration instructions, see

sections 6.3 and 6.17.)

• The MV will automatically write a message to indicate when the trend update rate has

been switched during memory sampling.

• The MV will automatically write a message to indicate when power has been

restored after a power failure that occurs during memory sampling.

Message Dsplay Optons

• When using horizontal or horizontal split display, messages can be displayed either

vertically or horizontally. (For configuration instructions, see section 6.10.)

• Messages can be displayed as a group in the upper left corner of the screen (list

display). (For operating instructions, see section 5.2.)

List display

Vertical display

1.4 Dsplay

This manual is related to the following products: