2-8

IM MV1000-01E

2.3 Optonal Termnal Wrng

Wrng to Optonal Termnals

WARNING

• To prevent electric shock, make sure that the power source is turned OFF.
• If you are going to apply a voltage of more than 30 VAC or 60 VDC to the

output terminals, use round crimp-on lugs with insulation sleeves on all output
terminals to connect the signal cables so that the wires won’t slip out even if the
screws loosen. Also, use cables that comply with double insulation requirements
(dielectric strength of 2300 VAC or more). For voltages below 30 VAC/ 60 VDC,
use cables that comply with basic insulation requirements (dielectric strength
of 1390 VAC or more). To prevent electric shock, attach the terminal cover after
wiring and make sure not to touch the terminals.

CAUTION

• Use the following circuit voltages for the connection to the alarm/FAIL/status

output terminal.
• When the connection is to Mains Circuits (primary AC power source circuits):

150 V or less

• When the connection is to circuits derived from Mains Circuits (secondary

circuits): 250 V or less

(keep the Mains Circuit voltage at less than 300 V, and use an isolation

transformer.)

• To prevent fire, only use signal cables with a temperature rating of 70°C or

above.

• Exposing the input and output signal cables connected to the MV to high tension

may damage the cables and the MV terminals. Do not stretch the cables to their
limit, and make sure that the terminals are not being pulled on.

• Do not short the transmitter power supply output terminal or apply external

voltage to it. Doing so may damage the MV.

• When using the transmitter power supply output terminal, do not use current that

exceeds the maximum output current (25 mADC). Doing so may damage the
MV.

Note

For remote control wiring, use shielded wires to reduce noise. Connect the shield to the
functional ground terminal or to the ground terminal of the MV.

Wrng Precautons

We recommend that you use crmp-on lugs (desgned for 4 mm screws) wth
nsulaton sleeves to connect to the optonal termnals.

Crimp-on lug (designed for 4-mm screws) with an insulation sleeve