beautypg.com

App index, Actons – Yokogawa Button Operated MV2000 User Manual

Page 46

background image

1-37

IM MV1000-01E

Feature Overv

ew

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

• Match Tme Tmer

You can set four match time timers. Specify the date/time using the method described

below. For each timer, you can select whether to use the timer once or continuously.
The timers are also used with the TLOG computation function (/M1 and /PM1 options).

Specfed Date/Tme

Descrpton

Month, day, hour

Occurs once a year.

Day and hour

Occurs once a month.

Day of the week and hour

Occurs once a week.

Hour

Occurs once a day.

Actons

• Lst of Actons

You can choose from the following actions.

Acton

Level/Edge*

Descrpton

MemoryStart/Stop

Level

Starts or stop memory sampling.

MemoryStart

Edge

Starts memory sampling.

MemoryStop

Edge

Stops memory sampling.

Trigger

Edge

Triggers the recording of event data. Valid

when recording event data in a triggered

mode. See the next page for more details.

AlarmACK

Edge

Stops alarm output.
Valid when the MV is configured to use the

alarm output release (AlarmACK) operation.

MathStart/Stop**

Level

Starts or stops computation.

MathStart**

Edge

Starts computation.

MathStop**

Edge

Stops computation.

MathReset**

Edge

Resets the values on all computation

channels.

SaveDisplay

Edge

Saves the display data currently being

recorded to internal memory. This is the

same as saving data by pressing FUNC.

SaveEvent

Edge

Saves the event data currently being

recorded to internal memory. This is the

same as saving data by pressing FUNC.

Message

Edge

Writes a message.
Can be executed during memory sampling.

Snapshot

Edge

Saves an image of the screen.

DisplayRate1/2

Level

Switches between the first and second trend

intervals.
Valid when the MV is set to be able to switch

between trend intervals.

ManualSample

Edge

Executes manual sampling.

TimerReset

Edge

Resets the relative timer. Timing begins

again from the point where the timer is reset.

See the next page for more details.

DisplayGroupChange

Edge

Changes the display group in the trend,

digital, or bar graph display.

Flag**

Level

When the event is a level operation, the flag

is zero for normal conditions and 1 when an

event occurs. When the event is an edge

operation, the value alternates between 0

and 1 whenever an event occurs.

The flag can be written in a calculation

expression of a computation channel.

PanelLoad

Edge

Reads the setup data file in the root directory

of the CF card and uses it to configure the

MV. See the next page for more details.

TimeAdjust

Edge

Sets the time to the closest hour. See the

next page for more details.

* For a description of level and edge, see “Miscellaneous” in this section.
**This is an option.

1.7 Event Acton Functon

This manual is related to the following products: