• Number of set ponts > Mes val, True val

Press the

Input soft key and enter the value.

For

Mes val (measured value), set a value that is greater than the previous value.

Press the

Measure soft key to set the current measured value to Mes val. If you press

the

Measure soft key when you are setting the calibration function for more than one

channel, the measured value of the channel set to

Frst-CH is used as the Mes val for

all channels.

Range of Selectable Values for Mes val and True val

• On Channels Set to Lnear Scalng

–30000 to 30000 (decimal place is the same as that set for the scale)

• On All Other Channels

The measurable range
Example: If the range is 2 V, –2.0000 to 2.0000

Note

• If you change the Mode or Range settings, calibration correction (the

Number of set ponts

setting) is switched Off.

• You cannot set calibration correction for a channel that is set to Skip.

3.9 Calbratng Input Values (/CC1 Opton)