5. The control unit acknowledges your input with a

double “beep” tone and shows Installer mode.

068 Forbikobler entry time

This function sets the time that the Forbikobler system
allows for entry. An optional output for a door lock can be
connected during this time. To change the property of the
Forbikobler entry time:

1. On the control unit, enter:

068

2. The LCD display shows: 068: Door Tm=5

3. Via the keypad, select from the following items

and press:

0

Door Tm=5
2 seconds

1

Door Tm=3
3 seconds

2

Door Tm=4
4 seconds

3

Door Tm=5
5 seconds

4

Door Tm=10
10 seconds

5

Door Tm=20
20 seconds

6

Door Tm=30
30 seconds

7

Door Tm=60
60 seconds

8

Door Tm=120
120 seconds

9

Door Tm=255
255 seconds

4. Confirm your input. On the control unit, enter:

.

5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.

069 Forbikobler door lock

Proceed as follows to change the property of the
Forbikobler door lock:

1. On the control unit, enter:

069

2. The LCD display shows: 069: Lock Timed

3. Via the keypad, select from the following items

and press:


0

Lock Timed
The door lock controlled by the
Forbikobler system is only open for a
certain time during the reset.

1

Lock Toggled
The door lock controlled by the
Forbikobler system is open during the
reset.

4. Confirm your input. On the control unit, enter:

.

5. The control unit acknowledges your input with a

double “beep” tone and shows Installer Mode.

070 Entry/exit behaviour on internal active
(C)

To change the zone property of the entry/exit zone at
internal active (C):

1. On the control unit, enter:

070

2. The LCD display shows: 070: C=FE = FE

3. Via the keypad, select from the following items

and press:

0

C=FE = FE
A zone programmed as entry/exit keeps
this property even for internal activation
and thus starts the entry delay time
when the zone triggers and during
active internal activation.

1

C=FE = NA
A zone programmed as entry/exit
changes its zone property during
internal activation to immediate and
triggers an alarm if the zone triggers
and during active internal activation.