60

UK

changes its zone property during
internal activation to entry/exit and
starts the delay time if the zone triggers
and during active internal activation.

4. Confirm your input. On the control unit, enter:

.

5. The control unit acknowledges your input with a

double “beep” tone and shows Installer Mode.

062 Behaviour of exist mode internal active
(B)

To change the property of the exit mode for internal active
(B):

1. On the control unit, enter:

062

2. The LCD display shows: 062: B=LEISE

3. Via the keypad, select from the following items

and press:

0

Low Tone
The acoustic signal during the exit
delay time is emitted at half volume.

1

Instant
During internal activation, the alarm
centre is internally activated
immediately – i.e., without delay.

2

Silent
No acoustic signal is emitted during the
delay time. Following expiry of the delay
time, the alarm centre emits a brief
signal.

3

B=A
The initial mode for internal active B is
as for the initial mode of overall active A

In a partitioned system

0

B=Timed
Activation of partition B after exit time
(command 65). A connected key switch
at the control unit shortens the exit time
when activated

1

B=Terminated
Activated via key switch connected to
the control unit. The exit time is

unlimited.

2

B=Final Door
Activation of the partition by closing the
last door detector

3

B=Instant
Active without delay time

4

B=Silent
Use command 65 for the exit time. The
control unit emits a double beep when
the time has expired.

5

B=Lock Set
Key switch (see command 39)

4. Confirm your input. On the control unit, enter:

.

5. The control unit acknowledges your input with a

double “beep” tone and shows Installer Mode.

063 Alarm behaviour for internal active (B)

To change the alarm property for internal active (B):

1. On the control unit, enter:

063

2. The LCD display shows: 063: B=Keypad

3. Via the keypad, select from the following items

and press:

0

B=Keypad
Only the control units are activated.

1

B=Internal
On alarm, the control units and the
internal alarm are activated.

2

B=Local
On alarm, the control units, the internal
alarm and the external siren are
activated.

3

B=Full
On alarm, the control units, the internal
signalling, the external sirens and the
telephone dialler are activated.

In a partitioned system

0

B=Keypad
Only the control units are activated.

1

B=Local
On alarm, the control units, the internal