beautypg.com

ABUS AZ4110 LCD Keypad for Terxon SX_MX Installation User Manual

Page 118

background image

14

UK

10.2 Control

units


The burglar alarm panel can operate with up to four
control units connected via a BUS.

The control units can be connected as a ring or star to
the alarm centre. Connect the control unit as follows:

To next control unit / alarm centre

Terminal connector strip: 0V
To next control unit / alarm centre

Terminal connector strip: 12V
To next control unit / alarm centre

Terminal connector strip: CLK (Clock)
To next control unit / alarm centre

Terminal connector strip: DATA (Data)


The length of the databus must not exceed 200m. For
connecting the control units, use a cable with a wire
diameter of min. 0.6mm.

Other devices that can be connected to the control
units:

ET: A switch for manual ending of exit delay time. The
contact is normally open (NO) and must be closed to
activate.
Ext. Tamper: Additional input on control unit to which
an external tamper contact (NC) can be connected.
The contact must be opened to trigger a tamper
alarm.

PANIC I/P (from panel version 2.04.0151): There
you can connect a panic button.


1

2

3

4

5

6

7

NOTE: The connection cables must be inserted in

the clamps from above

.

Coding of control units
Control unit 1:

Jumper not connected

Control units 2–4:

Jumper connected accordingly to
the pin numbers 2, 3, or 4.


Background lighting
Background lighting on:

Jumper connected.

coding of control units

background lighting


volume beeper

tamper contact

beeper

1

2

3
4

5

6

7