B.20 source:current:protection:tripped? query, B.21 source:list:dtime command, B.22 source:list:dtime? query – KEPCO KLN Series (750W, 1500W, 3000W), Main Contro Firmware Version 1.70 and higher User Manual
Page 99: B.23 source:list:rtime command, B.24 source:list:rtime? query, B.25 source:memory:cls command, B.26 source:memory:current:x command, B.20, Sour, B.21

KLN Series 051614
B-5
B.20
SOURce:CURRent:PROTection:TRIPped?
QUERY
SOUR:CURR:PROT:TRIP?
Syntax:
Short Form: SOUR:CURR:PROT:TRIP? Long Form: SOURce:CURRent:PROtection:TRIPped?
Description:
Returns a 1 if the protection circuit is tripped and a 0 if it not tripped.
Return Format:
Example:
SOURce:CURRent:PROTection:TRIPped? Returns 0 if OCP was not executed, 1 if OCP was exe-
cuted.
B.21
SOURce:LIST:DTIMe COMMAND
SOUR:LIST:DTIM
Syntax:
Short Form: SOUR:LIST:DTIM
Description:
Sets the output ramp-down time.
Argument:
Example:
SOURce:LIST:DTIMe 3.0 programs the output ramp-down time to 3.0 seconds.
B.22
SOURce:LIST:DTIMe?
QUERY
SOUR:LIST:DTIM?
Syntax:
Short Form: SOUR:LIST:DTIM?
Long Form: SOURce:LIST:DTIMe?
Description:
Indicates (in seconds) how long output voltage takes to reach zero from programmed
value.
Return Format:
Example:
SOURce:LIST:DTIMe? returns 3.00000E+00 to indicate ramp-down time is 3.0 seconds.
B.23
SOURce:LIST:RTIMe COMMAND
SOUR:LIST:RTIM
Syntax:
Short Form: SOUR:LIST:RTIM
Description:
Sets the output ramp-up time.
Argument:
Example:
SOURce:LIST:RTIMe 3.0 programs the output ramp-up time to 3.0 seconds.
B.24
SOURce:LIST:RTIMe?
QUERY
SOUR:LIST:RTIM?
Syntax:
Short Form: SOUR:LIST:RTIM?
Long Form: SOURce:LIST:RTIMe?
Description:
Indicates (in seconds) how long output voltage takes to reach programmed value.
Return Format:
Example:
SOURce:LIST:RTIMe? returns 3.00000E+00 to indicate ramp-up time is 3.0 seconds.
B.25
SOURce:MEMory:CLS COMMAND
SOUR:MEM:CLS
Syntax:
Short Form: SOUR:MEM:CLS
Long Form: SOURce:MEMory:CLS
Description:
Clears all memory locations used for storing and recalling power supply settings.
Argument:
None
Example:
SOURce:MEMory:CLS clears all memory locations.
B.26
SOURce:MEMory:CURRent:X COMMAND
SOUR:MEM:CURR:X
Syntax:
Short Form: SOUR:MEM:CURR:X
Description:
Sets the memory location defined by X to the current value
Argument:
Example:
SOURce:MEMory:CURRent:5 11.6 sets memory location 5 to 11.6A.