KEPCO KLN Series (750W, 1500W, 3000W), Main Contro Firmware Version 1.70 and higher User Manual
Page 15

KLN Series 051614
1-5
PROGRAMMING CHARACTERISTICS - DIGITAL
Command setting resolution
±0.002% of full scale
Command reading resolution
±0.002% of full scale
Command and D/A
setting accuracy
Voltage:
Current:
±0.1% ± 3C
(3)
at rated voltage
±0.5% ± 3C
(3)
at rated current
Command and A/D
Measurement accuracy
Voltage:
Current:
±0.2% ± 2C
(3)
at rated voltage (Average Measurement)
±0.5% ± 3C
(3)
at rated current (Average Measurement)
Command response time
20ms (After received)
(4)
RS-485 Digital Interface
(standard)
Baud rate:
Select 4.8K, 9.6K, 19.2K, 38.4K, 57.6K, or 115K (max)
Max number of units
connected to bus:
254
Max. effective control distance:
1000 meters.
GPIB Digital Interface
Optional
LAN Digital Interface
Optional
PROGRAMMING CHARACTERISTICS - ANALOG
Analog setting accuracy
Constant Voltage mode (CV):
Voltage:
Current:
± 5%
± 5%
Constant Current mode (CC):
Voltage:
Current:
± 5%
± 5%
Analog monitor accuracy
Rated voltage output:
10.00V ± 0.25V
Zero voltage output:
0.00V ± 0.25V
Rated current output:
10.00V ± 0.25V
Zero current output:
0.00V ± 0.25V
PHYSICAL CHARACTERISTICS
Weight
750W:
1500W:
3000W:
Less than 11.2 lbs (5.1 Kg)
Less than 19.84 lbs (9.0 Kg)
Less than 33.3 lbs (15.1 Kg)
Dimensions
750W:
1500W:
3000W:
8.46"W x 1.73"H x 18.5"D (215mm x 44mm x 470mm)
See Figure 1-2
16.93"W x 1.73H x 18.5"D (430mm x 44mm x 470mm)
See Figure 1-3
16.93"W x 3.46"H x 18.5"D (430mm x 88mm x 470mm)
See Figure 1-4
Source Power Connector
750W:
1500W, 3000W:
IEC 320 inlet
3-position terminal block
Load Connections
6V to 100V:
150V to 600V (750W):
150V to 600V (1500W, 3000W):
± bus bars with protective cover
5-position Euroblock
4-position terminal block
(2) C = 1 count of the last displayed digit.
(3) Programming time = Command response time + Output response time. The output response time differs for different models,
see Table 1-1. The analog programming input signal goes directly to the analog circuitry, so there is no command response
time delay for analog programming.
TABLE 1-2. KLN GENERAL SPECIFICATIONS (CONTINUED)
SPECIFICATION
RATING/DESCRIPTION