Yaskawa MP920 Communications Module User Manual
Page 88

5.5 CP-215 Transmission Definitions
5-27
5
2. Token Cycle Time, Setting, Max. Value, Current Value
Displays the Token Cycle Time Setting set in the Transmission Parameter Tab, as well
as the actual maximum and current values. In Offline Mode, data will not be displayed
in the “Max. Value” and “Current Value” boxes.
3. ST#
Displays the station number. Two asterisks (**) will be displayed for the local station
number. The local station number is determined by the number input in the Transmis-
sion Parameter Tab’s Own Station Number Box. The station number displays only the
number input in the Transmission Parameter Tab’s Max. No. of Stations Connected Box.
4. TYPE
Displays the I/O device name set in the Link Assignment Tab.
5. REG-No., SIZE
Displays the leading register number and amount of I/O data set in the Link Assignment
Tab.
6. SCAN
Displays the transmission mode set in the Link Assignment Tab.
7. LSTS
In Online Mode, the 215IF link status data is displayed in hexadecimal. In Offline
Mode, nothing will be displayed.
The following diagrams show the meaning of the link status data for other stations and
the local station.
a) Link Status Data for Other Stations
Fig. 5.3 Link Status Data (Other Stations)
F E DC B A 9 8 7 6 5 4 3 2 1 0
Link Transmissions: Reception Length Error
Link Transmissions: Timeout Error
Link Transmissions: Reserved
Link Transmissions: Reserved
Reserved
Link Map Registered Station
Initial Status (Nothing Received Since Reset)
Completed Normal Reception of Link Data
PLC Model Code (Corresponds to the content of the “TYPE” column.)
02: CP-3500H
05: CP-316
06: CP-916A
0C: CP-9200SH
14: MP920
0F: CP-916G
C2: RIO-05
C5: RIO-2000
C6: RIO-120
62: 215IF/INV
0D: CP-317
11: ACGC4000
12: CP-517
0E: CP-316H
16: CP-902