beautypg.com

Holding register write (extended) – Yaskawa MP920 Communications Module User Manual

Page 260

background image

B.1 Extended MEMOBUS Messages

B-11

B

„

Holding Register Write (Extended)

MFC: 20H

SFC: 0BH

Length: 06H+

SPARE

CPU No.

Data 1

Data n

(L)

(H)

(L)

(H)

(L)

(H)

(L)

(H)

(L)

(H)

Set the command length.

Command

Always 20H.

The SFC number is 0BH when holding registers are written.

Set 4 bits each for the destination CPU number and the source
CPU number.

Set the contents of the holding register to be written.

Set the leading address of the holding registers to be written.

Set the number of holding registers to be written.

7

0

No.of registers×2

No. of registers (n)

Reference No.

MFC: 20H

SFC: 0BH

Length: 08H

SPARE

CPU No.

Set the command length.

Response

The same SFC number as that specified in the command is

returned.
Set 4 bits each for the destination CPU number and the source

CPU number.

The leading addresses of the written holding registers are returned.

The number of written holding registers is returned.

(L)

(H)

Reference No.

No. of registers (n)

(L)

(H)

(L)

(H)

(H)

7

0

Always 20H.