6.4 Cables
6-11
6
6.4.2
RS-422/485 Interface Cables
• The power system, control system, and electrical system, as well as the transmission system, must
be wired separately.
• The RS-422/485 interface of the 217IF Module is an MR-8-pin connector (CN3).
• The maximum length of the RS-422/485 cable is 300 meters. This cable should be as short as pos-
sible.
• The RS-422/485 interface of the 217IF Module is not isolated. A malfunction may sometimes
occur, due to noise from the connected terminals. If noise is a problem, use a shielded cable or a
modem to reduce the noise.
• With the RS-422, insert terminating resistances as required. Be sure to insert terminating resis-
tance at the ends of the line.
• With the RS-485, use terminating resistances at both end stations of the transmission line.
Table 6.5 217IF RS-232C Transmission Line Connections
MP920 217IF (CN1, CN2)
Cable Connection and Signal
Direction
Remote Station
(D-sub 9-pin)
(Yaskawa Specifications)
Signal Name
Pin No.
Pin No.
Signal Name
FG
1
1
FG
SD (TXD)
2
2
SD (TXD)
RD (RXD)
3
3
RD (RXD)
RS
4
4
RS
CS (CTS)
5
5
CS (CTS)
DR (DSR)
6
6
DR (DSR)
SG
7
7
SG
CD
8
8
CD
ER (DTR)
9
9
ER (DTR)
MP920 217IF (CN1)
Cable Connection and Signal
Direction
PC/AT Compatible Personal
Computer
Signal Name
Pin No.
Pin No.
Signal Name
FG
1
1
FG
SD (TXD)
2
2
SD (TXD)
RD (RXD)
3
3
RD (RXD)
RS
4
4
RS
CS (CTS)
5
5
CS (CTS)
DR (DSR)
6
6
DR (DSR)
SG
7
7
SG
CD
8
8
CD
ER (DTR)
9
9
ER (DTR)
IMPORTANT