beautypg.com

6 modem-to-modem connection, 1 system configuration, 2 cable specifications – Yaskawa MP920 Communications Module User Manual

Page 225

background image

8 Example Communications Module Applications

8.6.1 System Configuration

8-34

8.6

Modem-to-Modem Connection

This section explains MEMOBUS Master/Slave communications with two modems.

8.6.1

System Configuration

The standard serial port (Port 1) of an MP930 located a distance away from the 217IF Mod-
ule is configured as a modem-to-modem system.

The engineering environment is provided by connecting the MPE720 Programming Device
to the CN1 port of the 217IF.

8.6.2

Cable Specifications

„

217IF Module

↔ Modem

MP930

↔ Modem Connection Cables

MP930

MP920

PS-01

CPU-01

217IF

Engineering

MPE720

MEMOBUS

RS-232C

Modem

Modem

217IF Module

Modem

D-sub 9-pin

D-sub 9-pin

Signal Name

Pin No.

Pin No.

Signal Name

FG

1

1

FG

TXD

2

2

TXD

RXD

3

3

RXD

RTS

4

4

RTS

CTS

5

5

CTS

DSR

6

6

DSR

SG

7

7

SG

N.C.

8

8

N.C.

DTR

9

9

DTR