6.4 Cables

6-13

6

„

RS-485 Wiring

Note: 1. The terminating resistance will be enabled by connecting terminals

5 and 6, and terminals 1 and 4 at the CN3 interface.

2. Connect the 217IF CN3 FG connection to the FG terminal of the

Power Supply Module, using a lead wire.

CN2

CN1

RUN

ERR

TRX1

TRX2

TRX3

CN3

217IF

RS232/422

Terminal

Terminal

Terminal

Terminal

(PLC, etc.)

(PLC, etc.)

(PLC, etc.)

(PLC, etc.)

RS-485

MP920

TX / RX

TX / RX

TX / RX

7

TX (+)

6

TX (-)

5

TXR

2

RX (+)

1

RX (-)

4

RXR

3

SH

8

SH

FG

217IF CN3

FG

Shield

1

2

For example, when a 217IF Module is
connected at intermediate position,
the wiring will be as shown below.

SH TX

(-)

(+) (-)

(+)

TX RX RX SH

3

6

7

1

2

8

1

2