Data address (param05) – Yaskawa MP920 Communications Module User Manual
Page 236

A.1 SEND MESSAGE Function (MSG-SND)
A-7
A
* Yes: Can be set, No: Cannot be set
Note: Only MW (MB) registers can be used as sending/receiving registers
during master operation.
MB, MW, IB, and IW registers can be used as coils, holding registers, input relays, and input
registers during slave operation.
The extended MEMOBUS functions can be used for communications between CP-316, CP-
317, CP-916A, and CP-916B via CP-215.
Data Address (PARAM05)
The data address setting differs according to the function code as shown below.
33H
MELSEC random buffer write
218IF only
No
34H to 3FH
Reserved by system.
No
No
40H to 4FH
Reserved by system.
No
No
50H or later
Not used.
No
No
(cont’d)
Function
Code
Meaning
215IF, 218IF,
MECHA-
TROLINK*
217IF,
Serial*
Function
Code
Function
Data Address Setting Range
215IF, 218IF,
MECHATROLINK
217IF, Serial
00H
Not used.
Not valid.
01H
Coil status read
0 to 65535 (0 to FFFFH)
1
02H
Input relay status read
0 to 65535 (0 to FFFFH)
1
03H
Holding register read
0 to 32767 (0 to 7FFFH)
2
04H
Input register read
0 to 32767 (0 to 7FFFH)
2
05H
Single coil status change
0 to 65535 (0 to FFFFH)
1
06H
Single holding register write
0 to 32767 (0 to 7FFFH)
2
07H
Not used.
Not valid.
08H
Loopback test
Not valid.
09H
Holding register read (extended)
0 to 32767 (0 to 7FFFH)
2
Not valid.
0AH
Input register read (extended)
0 to 32767 (0 to 7FFFH)
2
Not valid.
0BH
Holding register write (extended)
0 to 32767 (0 to 7FFFH)
2
Not valid.
0CH
Not used.
Not valid.
0DH
Discontinuous holding register read
(extended)
0 to 32767 (0 to 7FFFH)
3
Not valid.
0EH
Discontinuous holding register write
(extended)
0 to 32767 (0 to 7FFFH)
3
Not valid.
0FH
Multiple coil status change
0 to 65535 (0 to FFFFH)
1
10H
Multiple holding register write
0 to 32767 (0 to 7FFFH)
2
31H
MELSEC fixed buffer communications
0 to 32767 (0 to 7FFFH)
2
32H
MELSEC random buffer read
0 to 32767 (0 to 7FFFH)
2