Appendix D Wiring Communications

D.2.1 Panel-to-Panel Cable Connections

D-14

D.2 Indoor Panel-to-Panel Wiring

D.2.1 Panel-to-Panel Cable Connections

„

215IF Panel-to-Panel Cable Connections

The following figure shows a 215IF panel-to-panel cable connection example.

Fig. D.9 215IF Panel-to-Panel Cable Connection Example

• Connecting Signal Lines

Use panel-to-panel cables to connect the incoming and outgoing SRD+ and SRD- signal
terminals on each control panel as shown in the above figure.

• Connecting Terminating Resistances

Mount 75

Ω terminating resistances at both ends of the transmission line.

• Connecting Shielded Ground Trunk Cables

Connect the Es terminals of each control panel using daisy chain connections.

Use a shielded ground trunk cable of 8 mm

2

or greater.

Using a ground wire of 8 mm

2

or greater, ground the shielded ground trunk cable to an

independent ground pole with a ground resistance of 100

Ω or less.

+

-

+

-

SRD

SRD Es

+

-

+

-

SRD

SRD

Es

+

-

SRD

Es

+

-

SRD

E

75

Ω

75

Ω

Shielded ground trunk cable: 8 mm

2

Panel-to-panel cable

Independent ground pole:
100

Ω or less

8 mm

2

8 mm

2